Parameter Description
Parameter Description
118
Please pay attention to the Gain setting during the process of PID Gain setting for it is possible that
the output current can not be limited absolutely.
Under PID control, the output frequency is also limited between the maximum frequency and the
minimum frequency.
● Please refer to the instruction of P.60 about the input signal filter on terminal 4-5 and terminal 2-5.
● The sketch map of PID function is as follows:
s
T : Sampling period10ms
Parameter
Factory
Setting
Setting
Range
Remarks
170 0 0, 1, 2
0 PID function non-selected
1
The target value is determined by P.225. The feedback
value is determined by the voltage of terminal 2-5.
2
The target value is determined by P.225. The feedback
value is determined by the voltage of terminal 4-5.
171 0 0,1
0
Negative feedback control. The calculation for the
deviation is target value minors the feedback value.
When an increase in the output frequency will increase
the feedback value, select this setup.
1
Positive and feedback control. The calculation for the
deviation is feedback value minors the target value.
When an increase in the output frequency will decrease
the feedback value, select this setup.
172 20 1~100
This gain determines the proportion controllers impact on
feedback deviation. The greater the gain, the faster the
impact. Yet a gain that is too big will cause vibration.
173 1s 0~100s
This parameter is use to set integral controllers integral
time. When the integral gain is too big, the integral effect
will be too weak to eliminate steady deviation. When the
integral gain is too small, the system vibration frequency
will increase, and therefore the system may be unstable.
174 0ms 0~1000ms
This gain determines deviation controllers impact on the
amount of change of the deviation. Appropriate deviation
time can reduce the overshooting between the proportion
controller and the integral controller. Yet when the deviation
time is too large, system vibration may be induced.
175 0 0~100% ---
176 30s 0~600s ---
177 0 0, 1,2
0 Free stop
1 Decelerate and stop
2 Continue to run when the alarm goes off

Table of Contents

Other manuals for Shihlin electric SS2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SS2 Series and is the answer not in the manual?

Shihlin electric SS2 Series Specifications

General IconGeneral
BrandShihlin electric
ModelSS2 Series
CategoryInverter
LanguageEnglish

Related product manuals