Display Possible cause Remedy
Waiting for configuration
or conf
iguration not
completed
b
T
he display goes out automatically once the
configuration has been successfully trans‐
ferred.
If the display does not go out:
b
Check the system configuration using the
CDS. Transfer the corrected configuration to
the device again.
b
Check whether the configuration saved in the
system plug is compatible with the safety laser
scanner.
Waiting for restart of the
de
vice
b
S
witch off the voltage supply for the safety
laser scanner for at least 2 seconds and then
switch it back on.
or
Fault in the external
de
vice monitoring (EDM)
b
Chec
k whether the contactors are working cor‐
rectly or have been wired incorrectly and rec‐
tify any error.
b
Additionally if is displayed: Switch off the
device, wait at least 3 seconds, then switch
the voltage supply back on.
Error in the control
s
witch for restart or
reset
b
Chec
k the functionality of the control switch.
The pushbutton may be defective or stuck.
b
Check the wiring of the control switch for
short-circuit to 24 V.

Sensor head faulty
b
Switch off the voltage supply for the device for
at least 2 seconds and then switch it back on.
If the display does not go out:
b
Send the device to the manufacturer for
repair.

I/O module faulty

Configuration memory in
t
he system plug defec‐
tive

A second device which
is connec
ted via EFI is in
the fault state.
b
Chec
k the connected device and the connec‐
tion.

Overcurrent at OSSD
connec
tion 1
b
Chec
k the connected switching element (con‐
tactor, relay) and replace if necessary.
b
Check the wiring for short-circuit to 0 V.

Short-circuit to 24 V at
O
SSD connection 1
b
Chec
k the wiring for short-circuit to 24 V.

Short-circuit to 0 V at
O
SSD connection 1
b
Chec
k the wiring for short-circuit to 0 V.

Overcurrent at OSSD
connec
tion 2
b
Chec
k the connected switching element (con‐
tactor, relay) and replace if necessary.
b
Check the wiring for short-circuit to 0 V.

Short-circuit to 24 V at
O
SSD connection 2
b
Chec
k the wiring for short-circuit to 24 V.

Short-circuit to 0 V at
O
SSD connection 2
b
Chec
k the wiring for short-circuit to 0 V.

Short-circuit between
O
SSD connection 1 and
2
b
Chec
k the wiring and rectify the error.

General OSSD wiring
er
ror
b
Chec
k the complete wiring of the OSSDs.
Device is addressed as
gue
st
Not an error. The symbol is displayed for approx.
2 seconds when a device that is addressed as a
guest is switched on.
10 TROUBLESHOOTING
102
O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store 8012029/ZA20/2019-11-14 | SICK