In the CS1140 fire detection system there are 5 communication levels:
I-Bus
internal data bus between individual modules in the control unit (line modules, control
modules etc.)
C-Bus
local data bus between control unit(s), control console(s) and Gateway(s)
D-Bus (or AnalogPLUS-Bus or collective detection line)
local detector bus; connects the detectors to the control unit
LON-Bus
local data bus for text display and control terminals, mimic display converter and LON
I/O card
Data Bus
local data bus for parallel indicator panel, synoptic panel or relais
Gateway
CK11
Control terminal
CT11
E3H020
DMS7000
LMS modula
r
(Host system)
C-Bus
CERLOOP / CERBAN
E3I040
I-Bus
LON-Bus
Data bus
I-Bus
Control unit CC11, CI11
E3M... E3M... E3M...
Line modules
E3X10.
or
AlgoPilot B3Q...
CPU:
interactive
detectors
collective
detectors
AnalogPLUS
detectors
B3Q580/
B3Q590/
B3Q595
E3I040
LON-Bus
D-Bus
AnalogPLUS-Bus
collective
detection line
K3I050
B3R051
or
K3R072/
K3G060
K3I110
Data bus
In-/outputs