25 Control modules
Application of control modules
Activation of fire control installations
(shutting-down ventilation, closing fire dampers etc.)
Activation and monitoring of alarm device
Activation and monitoring of remote transmission equipment
Activation of Mimic Display panels
Overview of the available modules with control outputs
ÁÁÁÁ
Modules
ÁÁÁÁÁÁ
Monitored control lines
for alarm devices
ÁÁÁÁÁÁ
Driver outputs
programmable
ÁÁÁÁÁÁ
Contact outputs
(volt free)
programmable
ÁÁÁÁÁÁ
Remote transmission
interface
to remote transmission
equipment
E3X10.
2
8 + 1
E3G070
2
7 1) 2)
E3L020
16 1)
E3G050
8
E3G060
6 5)
K3R072
48 3)
K3G060
24 NO contact 4)
K3I110
16 NO contact 5) 6)
1) can also be used as control inputs (e.g. ’acknowledgement’)
2) these inputs/outputs also serve for the activation of the remote transmission equipment
3) for activation of Mimic Display panel, connected to the operating unit B3Q... or K3I050 (no I-Bus module) for details see page 70
4) applicable only with K3R072 Details see page 71
5) programmable
6) LON-Bus module Details see page 73
25.1 Means of linking
Any statuses of entry nodes can be linked to control ZONES
Normally, only 1 control ELEMENT is contained in 1 control ZONE (= control output)
A user text is allocated to each control ZONE
E3G050
K3I110
E3L020
E3X10.
E3G070
E3G060
Acquisition level Control level
AREA
SECTION
ZONE
Statuses:
– alarm
– info
– switched off
– on detector TEST
– fault
– etc.
Control
ZONE
Digital input
’active’
Operating level
Acknowledgement circuit
Visible statuses
– active
– switched off
– executed (’Acknowledgem.’)
– fault
Operatable functions:
– switch on/off
– activate/de-activate
not
monitored
monitored
interactive
AnalogPLUS
CBA8000/TS9000
MS9i
collective