8 Specify hardware required
In order to be able to specify the hardware required, system key data must be specified
according the following procedure:
1. Specify number and type of detection lines
dependent on:
Detector series
Number of detectors, input and output modules
Building structure
2. Specify number and type of fire control installations
dependent on:
The fire protection installations to be activated
Location of the contacts (centralized or decentralized)
Individual types of contact (250VAC/10A or 30VDC/1A)
3. Specify number and type of operating units
dependent on:
Operating concept
Language on the operating unit front terminal
Parallel indicator panels, fire department control panels
4. Specify Accessories required
dependent on:
Printer interface and printer
PSA/Pager interface
Remote transmission equipment
Gateway, etc.
5. Specify emergency power supply battery capacity
dependent on:
Total quiescent current
Required emergency current operating period (according to country)
Type of remote transmission
6. Specify type of cabinet
dependent on:
Number and type of modules
Required accessories
Number and type of sets of batteries
7. Provide configuration sheet/sheets (see page 104 ff)
Select sheets corresponding to the configuration
Complete everything

Table of Contents

Other manuals for Siemens Cerberus CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus CS1140 and is the answer not in the manual?

Siemens Cerberus CS1140 Specifications

General IconGeneral
BrandSiemens
ModelCerberus CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals