29.2 Option emergency operation link E3G110
Enables automatic activation of extinguishing through interlinked areas even if the main CPU malfunctions.
The detectors in the extinguishing SECTION must be distributed over 2 independent detection lines.
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
E3M071
B3Q440
E3G080
K1
CPU
E3X10.
or
B3Q...
E3G110
K1
24/5V
1......4
K1
ST1 ST8
ST10
K1
E3M071
ST10
K1
I-Bus
Manual activation
Interactive
detectors
CC11, CI11
Note: Only E3M060 (MS9i), E3M071 (interactive), E3M171 (interactive Ex),
E3M080 (collective) and E3M111 (AnalogPLUS) are equipped with connector «ST10»
DM1103/04
E3G110
Z1I030/050
29.3 Key data
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Sector valve ’delayed’
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– activation delayed 0..240s
– permissible operating time 0..240s or until reset
– monitored line
– line can be adjusted to sector valve
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Main valve ’not delayed’
(activation of pneumatic circuit)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– permissible operating time 0..240s
– monitored line
– line can be adjusted to main valve
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Alarm horn
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– can be switched off via extinguishing operating unit or control unit
– monitored line
– programmable actuating mode staedy/pulsating
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Illuminated warning panel
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– can be switched off separately or is active until reset
– monitored line
– programmable actuating mode staedy/pulsating
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Manual actuation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– direct to E3G080
– also functions with ’Emergency operation’ control unit
– line monitored
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Automatic activation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– via detector control unit, can be parameterized upon alarm
alternative from:
– detectors in the same ZONE
– detectors in different ZONES
– detectors in the same or in different ZONES
– all detector systems can be installed (interactive / AnalogPLUS / collective)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Stop/blocking button
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– separate monitored line
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Signal contact ’Extinguishing agent leak’
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– separate monitored line
Signal contact ’Extinguishing blocked’
– separate monitored line
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Signal contact ’Extinguishing activated’
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– separate monitored line
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
On-site operation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– by means of ’Extinguishing’ operating unit B3Q440
– use recommended, but not essential
– max. 4 operating units possible
– via LON data bus with monitored line
– length of line up to 600m
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Fire control installation
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– via control output control unit
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
Special features
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
– autonomously functioning I-Bus module
– integrated emergency operation function
– parameters set via AlgoWorks
– user functions stored on E3G080
– several extinguishing SECTIONS mutually interlocking
– automatic calibration function