30 Printer interface
30.1 Features
Provided with station types CT11, CI11, CC11
Designed for Cerberus printer or commercially available printer with ISO or EPSON
character set
Additional hardware required for level adaptation according to application
Printer B2Q191 can be connected direct (when mounted inside cabinet)
The printer can be individually switched on/off via the operating unit
Always allocated to all existing AREAS for the station used
Individual parameterization for each printer interface
The event memory can be printed only if the printer is connected to a station CI11 or CT11
30.2 Application variant CT11
AlgoPilot B3Q...
AlgoPilot B3Q...
Requirement:
The printer B2Q191 must be in the same cabinet as the
operation unit B3Q... or in an immediately adjacent cabinet
With this application:
Ground wire to be removed from ’K3-5’ and connected to
chassis ground (otherwise results in ground fault)
in cabinet H26/H28
I-Bus
E3I020
RS232
CT11
ST2
F20A020
ST1
ST2
to printer
B2Q191
24VDC
K2
K3
or
I-Bus
B2Q191
ST2
F20A410
A3
max. 1m
24VDC
K2
(TTL)
in cabinet H26/H28
(9...36V
DC)
max.1000m
F20A020
ST2
E3I020
Z1B020
B3Q...
C-Bus
C-Bus
F20A410
B2Q191
B3Q...
CT11