33.3 Quiescent current table
quiescent current when on battery operation (24V)
as basis for individual calculation of emergency power supply
the current for the 5V supply is included in these values
Module Quiescent current at 24VDC (typical) Additional current with alarm condition
B2F020
B1F120
0 0
B2Q191/B1Q101 33mA max.1A only during printing
B3Q321 17mA +5mA
B3Q440 25mA +10mA
B3Q4.. 100mA LCD backlight ’inactive’ (active = + 100mA) + 125mA
B3Q560 75mA LCD backlight ’inactive’ (active = + 120mA) + 185mA
B3Q6../565 100mA LCD backlight ’inactive’ (active = + 200mA) + 230mA
B3Q580 20mA +80mA
B3Q590/595 18mA + 100mA
B3R051 40mA all LEDs inactive + 2mA per activated LED
E3C011 20mA 0
E3G050 10mA all relays inactive + 11mA per activated relay
E3G060 25mA all control lines terminated
+ 23mA per activated control line, without
external load
E3G070 25mA control line ’Horn’ terminated + 34mA without external load (horns etc.)
E3G080 35mA all lines terminated + 25mA without external load (valves, horns, etc.)
E3G091 0 all channels inactive + 9mA per activated channel
E3G110
0 only active for emergency operation and
alarm
+ 15mA per activated channel for emergency
operation
E3H020 100mA 0
E3I020 25mA 0
E3L020 22mA + .. mA depends from the activated device
E3L030 18mA + 40mA without external load (FBF, HM, FSK)
E3M060 155mA (=120mA + 0,7mA per MS9i element) 1) 0
E3M071
115mA (=50mA + 0,5mA per D-Bus device) 1)
(without external 24V load)
0
E3M171
70mA with 32 detectors (=50mA without detectors
+ 0,5mA) per D-Bus device 1)
0
E3M080 85mA 37mA + 6mA per terminated line + 10mA per line in alarm
E3M111
210mA (=50mA + 0,31mA per D-Bus device) 1)
(A+ without external 24V load)
0
E3M120 8,5mA +1,3mA for each detector address 0
E3M220
227mA 247mA with 82kW terminated
+ 120mA per line in alarm condition
E3X101 100mA control line ’Horn’ terminated + 40mA without external load (horns, etc.)
E3X102/103 120mA control line ’Horn’ terminated + 50mA without external load (horns, etc.)
K1D012 25mA 0
K1D081 50mA 0
K1D121 50mA 0
K1D140 25mA 0
K1H021 50mA 0
K3G060 6mA + 3mA per relay
K3R072 40mA
+ 2mA per activated LED
0 per activated relay
Z3B171 0 + 27mA per activated relay
E3I040 15mA without external 24V load 0
K3I050 15mA + 0mA or 4mA per activated LED
K3I090 50mA 0
K3I110 24mA max. 184mA all Rel. activated incl. service LED
+ 10mA per activated relay
+ 0,5mA per input with closed contact
1) only valid for device with APMK = 1 / IMK = 1 (multiply value for devices > 1). Example DC1151: 0,5mA x 12 = 6mA
33.4 Available emergency power supply batteries
AX1201 225487 Battery 12V/27Ah capacity based on battery make ’ALARMCOM’ (FIAMM)
AX1209 462936 Battery 12V/42Ah ”
AX1210 475570 Battery 12V/15Ah
AX1212 484325 Battery 12V/12Ah