e4595e5
11
Fire & Security Products
Siemens Building Technologies Group
05.2003
5.1 Bus overview
Field of application
Speed of
transmission
Length of line
Number of users
connected or
Number of wires
Type of cable
Loop line
T-branch
Network structure
Scanning
Principle
Special feature
Features
local system bus
twisted
Short-circuit proof
master/master
C-Bus
57kBaud
max. 1000m
(G51 ø0,8: 1400m)
...16
2
(+3 wires for
1)
yes
each user connected
with line separator
event-controlled,
presence monitoring
serial Bus
– Cerberus protocol
– collision detection
– Manchester coding
I-Bus
inside control unit
1000kBaud
max. 3m
(only inside cabinet)
...16
26
flat cable
master/slave
cyclic,
event controlled
– Cerberus protocol
– SPI/Motorola
C-Bus
D-Bus
interactive
for interactive detectors
4,8kBaud
AnalogPLUS-Bus collective line LON-Bus
see document e1508
...128
2
twisted
as required
yes
master/slave
– typ. all 3s
– interrupt on alarm
cyclic
– Cerberus protocol ’K51’
– serial 8bit
sensor/actor-Bus
detector parameter
download
– Cerberus protocol ’K31’
– serial 8bit
sensor/actor-Bus
– start-up: daisy-chain
– typ. all 64s
– interrupt on alarm
cyclic
master/slave
yes
via T-branch module
twisted
(un-twisted permissible)
2
2 messages/sec
for AnalogPLUS detectors for collective detectors
(direct current signal)
1 address
(max. 25 detectors)
2
twisted
no
master/slave
– current gain principle
– voltage levels
conventional
78kBaud
max. 500m
as free topology
max. 1000m
as stub line
2
twisted
no
local data bus
event-controlled
– Echelon Chip
network
for floor indicator panels
C-Bus devices
I-Bus modules
DBus devices (interactive)
...128
DBus devices (AnalogPLUS)
...32
LON-Bus devices
master/slave
(LON protocol)
– Cerberus specific
telegram
presence monitoring
(all 60s)
(max.50/150/250/4µF)
(max.150/300nF)
(max.120/300nF)
Data Bus
local data bus
parallel ind. panel, synoptic
panel or relais
max. 1000m
...24
max. 8 addresses
6
(+ 3 wires supply)
twisted
yes
(see page 72)
serial bus
– Cerberus protocol
SPI-Bus 2KHz
master/slave
– typ. all 250ms
cyclic
addresses
emergency operation)
each user connected
with/without line separator
see document e1508
each user connected
with line separator
see document e1508
(un-twisted permissible)
1) calibrated according to cable impedance: 50W (MICC) / 110W (G51, ø0.8mm, not shielded)

Table of Contents

Other manuals for Siemens Cerberus CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus CS1140 and is the answer not in the manual?

Siemens Cerberus CS1140 Specifications

General IconGeneral
BrandSiemens
ModelCerberus CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals