Fire & Security Products
Siemens Building Technologies Group
05.2003
14 CC1142/43 in cabinet H67...
H Extendable system control unit
H With separate main CPU (E3X10.)
H Separate connection block
H Space for accessories
H Batteries as required either 2x 12V/27Ah or 2x 12V/42Ah
H Control terminals usually connected separately
H (installation possible in door)
H Door right hinged with lock (type DOM)
H67G601/611:
Set with
– door
– frame
– module chassis
– mains terminals
– battery supporting plate
– relay rail
Z3I350
Z1I070 oder Z1I040 oder
Z1I050
aufsteckbar im
Anschlussfeld
Einschub
E3X10.
B2F020
H67E101
AX12..
AX12..
B3R051
B3Q321
H23B040
H23B010
300
1130
434
H67G601
H67G611
Control terminal
installed separately
B3Q...
Comments:
– E3I020 if used mount
at position 32!
– B2F020 fits any mo-
dule space
Mounting of E3X10.:
Terminal block for
E3X10. containing in
cable set Z3I350
+ 2 x Z1I030
If Z3I041 or B3P020
is used, on Pos. 36
E3M060/071/171/120
and E3C011 not pos-
sible!
EMC Precaution:
Relative to each E3X10.
and E3C011 module po-
sition, two positions to
the right and two posi-
tions to the left must not
be fit with either E3I040
or E3G080 modules
Connection panelModules
Batteries
recommended space allocation
absolutely esssential
Supplied with cabinet sets H67G601/611
Important:
Comply with max. permissible number of
’nodes’ + I-Bus modules!
for details see chapter 7
Special feature:
H67E100 has 3 different hole patterns for mounting. As a
result, the relationship between connection block / modules
batteries can also be arranged differently
see page 38
02
62 65
H67G601 or H67G611
03
04
12 1311
32 33 34 35 36
E3I020
E3L020
Z1I050
E3L020
Z1I050
42 43 44 45
E3M...
Z1I...
E3M...
Z1I...
E3...
Z1I...
E3...
Z1I...
52 53 54 55 56
E3M...
Z1I...
E3M...
Z1I...
E3M...
Z1I...
E3M...
Z1I...
31
E3H020 + 2x Z1I050
21
Z3I330Z3I330
Z3I330
(for E3X10.)
Z1I050
Z3I330Z3I330
Z3I450
B2F020
14
E3...
Z1I...
E3...
Z1I...
61
E3...
Z1I...
AX1209
AX1201
AX1209
AX1201
cable duct
Mains
terminals
cable duct
(Battery 12V)
or or
01
Z3I330
Z3I570
max. 8
37
47
E3...
Z1I...
E3...
Z1I...
57
E3...
Z1I...
38
48
E3...
Z1I...
E3...
Z1I...
58
E3...
Z1I...
Details on cabinet H67...
see page 55
37
Z3I450
Mains
terminals
04
14
Z3I330
1)
1)
Fire control relay
–one or two connection cables Z1I070, Z1I040 or
Z1I050 are required for each module:
Line modules see page 59
LON module see page 72
Control modules see page 66
Extinguishing modules see page 79
Interfaces see page 75, 82, 86
One Z3I330 terminal block has space for:
either
–2x Z1I050 or
–8x Z1I070 or
–4x Z1I040 or
–1x Z1I050 and 2x Z1I040
1) Protection elements see page 95
or
8xZ3B171
Z3I330
or
8xZ3B171
(Battery 12V)
E3X10. + 2 x Z1I030 + Z3I350