e4595e24
59
Fire & Security Products
Siemens Building Technologies Group
05.2003
24 Line modules
There are different line modules for the various detection systems:
E3M071 interactive detectors
E3M171 interactive ’Ex’ detectors
E3M120 CBA8000/TS9000 detectors
E3M111 AnalogPLUS detectors
E3M060 MS9i detectors
E3M080 collective detectors (conventional detectors)
24V
max. 500mA
I-Bus
E3M071
E3X10.
ST10
24V
max. 500mA
ST10 = connector
for special applica-
tion (E3G110)
see page 80
E3M060
ST10
E3M080
ST10
Detector system
AlgoRex
interactive
AlgoRex
AnalogPLUS
MS9i
MS9iPLUS
MS716i
AlgoRex collective
MS6/7/9
(MS6: only detectors
without bulbs as AI)
Number of lines
1 4
18
No. of addresses
1 x 128
4 x 128
1 x 50 8
Loop line
−
Stub line
Short-circuit
separator
in each manual call
point and
input/output module
detectors
with/without
in each device
in each
device
−
Special features
D Any number of
T-branches can
be used
D Separate supply
output 24V for in-
put/output mod-
ules
D The response in-
dicator output can
be programmed at
the detector
D max. 8 T-branches via
DC1135 module
D Separate supply output
24V for input/output
modules
D Line short circuit can
be evaluated as a
fault or as an alarm
E3M080E3M071
E3M111
E3M060
Z1I030/050
Z1I020/040
24V
max. 500mA
E3M111
Z1I060/070
(only for CH)
1 2.............8
E3M171
ST10
AlgoRex
interactive
Ex
1
1 x 32
−
−
ST10
Z1I060/070
E3M171
E3M120
4
4 x 119
−
CBA8000
TS9000
in each
device
1........4
E3M120
D Any number
of T-
branches
can be used
D The re-
sponse indi-
cator output
can be pro-
grammed at
the detector