25.7 Relay outputs station type CT11 and CI11
AlgoPilot B3Q...
Z3I530
24V
Data bus
max.1000m
(Adapter)
24V
F12A100
or
F12A470
AlgoPilot B3Q...
Parallel branching permissible
for details see document e1260
(not monitored)
K3R072
1
48
1
24
24 outputs
max. 30V/1A
1
24
24 outputs
max. 30V/1A
K3R072
max. 24 units,
however max.
8 addresses
1
48
1
24
24 outputs
max. 30V/1A
1
24
24 outputs
max. 30V/1A
External potential
(switchable via jumper X1......X24)
)/*
)/*
1)
1)
1)
K3G060K3G060
K3G060K3G060
max. 24 units,
however max.
8 addresses
Flat cable supplied with K3G060
Flat cable supplied with K3G060
K3G060:
G 2 K3G060 can be connected to each K3R072
G 24 volt-free relay-make contact
G Contacts not monitored
G Contacts can be individually connected via jumper to externally supplied V+ or V– potential
24 Relay outputs
24 Relay outputs
Housing supplied by customer
K3G060
K3G060
K3R072
Modules
K3R072 528605 Mimic Display activation
K3G060 528786 Relay card option to K3R072
Z3I530 484972 Adapter for K3R072/B3R051 to adapt flat cable to terminals
F12A100 495275 Flat cable Micro 12-pin, 0.4m from AlgoPilot B3Q... to K3R072/B3R051
F12A470 495288 Flat cable Micro 12-pin, 1.5m from AlgoPilot B3Q... to K3R072/B3R051

Table of Contents

Other manuals for Siemens Cerberus CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus CS1140 and is the answer not in the manual?

Siemens Cerberus CS1140 Specifications

General IconGeneral
BrandSiemens
ModelCerberus CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals