Special structures now need to be counted equivalent to the following number of
devices:
Structure Number of de-
vices
S D-Bus participants with an own D-Bus address (e.g. DOT1151,
DO1131, DM1154, DCW1151, DOW1171...)
1
S Each used input or output of interactive or AnalogPLUS I/O devices
Example: DC1157 with 3 Inputs 6 devices
DC1154 with 1 output and 1 input for confirmation mes-
sage 4 devices
2
S Purely logical controls: Each ’element command’ or ’zone control’
not directly connected to a channel
2
S Collective lines (e.g. 1 line of module E3M080)
2
S Inputs of modules (e.g. E3X10x –> I4, E3L020 –> I2,
K3I110 –> LONin, external LON device –> LONin)
2
S Outputs of modules (e.g. E3X10x –> Q3, E3G050 –> Q1,
K3I110 –> LONout, external LON device –> LONout)
2
S Parallel indicator terminal/synoptic (equipped with up to 384 LEDs /
relays)
20
7.1.2 Limits in the logical structure
The limits in the logical structure are given by the node-type, by the highest possible CSX
number and the maximum amount of display-digits. These limits are given by the system
and are independent of the memory capacity.
Table ’Limits of the logical structure’
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Maximum rating
AREAS per STATION
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Maximum rating
SECTIONS per AREA
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Maximum rating
ZONES per SECTION
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Maximum rating
ELEMENTS per ZONE
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
... 4
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
... 255
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
... 255
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
... 99
1)
1)
International
5:
...
255
7.1.3 Maximum number of criteria in zones control 4 and 6 (RAM)
To trigger a zone control 4 or 6, 1 to 16 criteria can be programmed.
Each criterion requires a certain amount of memory. Therefore the maximum number of
criteria is limited according to the following graphs.
Important:
If CPU-overlapping controls are used (zone control 6) all criteria which are NOT located
in the same control unit as the control zone have to be counted twice: once in the control
unit they are located and once in the control unit the zone ’control 6’ is located.
Notes: To optimize the performance of your system minimize the number of
CPU- overlapping controls as much as possible.
A maximum of 40 CPU overlapping controls (zone control 6) are admissi-
ble per C-Bus.
no
yes
reduce number of
nodes or use an
additional station
number
of nodes
< X ?
no
yes
select station
with higher ca-
pacity or use an
additional station
number
of controls
< X ?