5
Operation
ALARM procedure
104
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
Example with AVC
The following conditions apply for the example:
l 'AVC' is activated.
l 'Manned operation' operation mode is set.
l The 'Intervention text' allows the fire location to be investigated
l This is a major incident.
l The FT2080 is closer to the fire location than the manual call point.
l Remote transmission is not available.
w An alarm event activates local alarming and starts the time t1 for manned
monitoring. The time t1 is shown in the 'Fire Brigade in' status information
in mm:ss.
1. Press 'Acknowledge' on the Person Machine Interface or in the event
command list (ECL).
a The investigation time t2 starts and is shown in the 'Fire Brigade in' status
information in mm:ss.
a The buzzer is switched off.
2. Read the status information.
a The status information 'Fire Brigade in' is displayed in mm:ss.
3. Press 'Show intervention text' in the ECL.