Operation
5
105
Building Technologies A6V10380629_en--_a
Fire Safety 2015-09-10
a The 'Show intervention text' opens.
a Investigating the fire location is permitted.
4. Read off the fire location.
5. Go to the fire location.
a There is a fire.
6. Press 'Alarm delay off' in the ECL.
a The 'Call Fire Brigade !' status information is displayed.
7. Alert the fire brigade by telephone.
a Global alarming is activated.
Example without AVC
The following conditions apply for the example:
l 'Manned operation' operation mode is set.
l The 'Show intervention text' allows the fire location to be investigated
l This is a minor incident.
l Remote transmission is not available.
w An alarm event activates global alarming. The 'Call Fire Brigade !' status
information is displayed.
1. Press 'Acknowledge' on the Person Machine Interface or in the ECL.