Closing the connection compartment / connection duct
180 NXAIR / 40 kA 110-0084.9 / 15
Fig. 257: 2 links on panel base
Fig. 258: Correct position of link
Make sure that the air guide (1) of the ventilation duct is folded upwards.
Fig. 259: Ventilation duct with air guide folded upwards
(1)
Air guide folded
upwards
(2)
Bottom side
Set the ventilation duct down centrally on the base frame of the panel. The side of the
ventilation duct to which the air guide is fixed must adjoin to the vertical partition.
Fig. 260: Set the ventilation duct down centrally on the base frame of the panel
Tighten the front bolts at the base frame hand-tight. Tighten the bolts with a tightening torque
of 25 Nm.