7 Operation at Use of a PC
7.3 Configuration of the Device
127SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
7.3.3.2.2 Group Indications
In the Select automation functions menu, up to 4 Group indications can be parameterized and each of them
can be assigned up to 4 logically linked single-point indications. The single-point indications can be inverted.
Default Settings and Setting of the Group Indications
NOTE
Which quantities are offered in the Measurand list box depends on the configured network type. The Network
type is specified in the Process connections submenu, AC measurement input/output window, see AC
Measurement.
Table 7-7 Group Indications
Parameter Default Setting Setting Range
Source -none- Acc. to list box
(see Operating Parameters)
Source inverted no no
yes
Logic operation NONE NONE
OR
AND
Group indication name Group Indication x
(x = 1 to 4)
Any