12 Technical Data
12.2 Test Data
232 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
12.1.5 General Data
12.2 Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
Battery Type PANASONIC CR2032 or
VARTA 6032 101 501
Voltage 3 V
Capacity 230 mAh
Typical life For operation with permanently applied
supply voltage:
10 years
For operation with sporadically interrupted
supply voltage:
a total of 2 months over a 10-year period
Internal memory capacity 2 GB
Degree of protection
DIN rail housing IP20
Panel flush mounting (front) IP40 (with display, without door)
IP51 (with display and door)
Terminals IP2x
Ambient temperature 23 °C ± 2 °C
Relative humidity 40 % to 60 % RH
Supply voltage V
PS
± 1 %
Phases (3-wire network) 3
External continuous magnetic fields DC field: 40 A/m
AC field: 3 A/m
DC components V/I none
Signal waveform sinus
Frequency 50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Voltage magnitude Udin ± 1 %
Flicker Pst < 0.1 %
Unbalance (all channels) 100 % ± 0.5 % of Udin
Harmonic 0 % to 3 % of Udin
Interharmonic 0 % to 0.5 % of Udin