11 Failures and LED Indications
11.2 Commissioning during Failures
219SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
11.2 Commissioning during Failures
11.2.1 Automatic Start of the Boot Loader
If a firmware update has failed or the device startup was unsuccessful, Internet Explorer will automatically open
the HTML page Boot Loader.
Figure 11-1 Boot Loader
Starting User Interface without
Loading a New/Different Firmware
Click Run Application. The following message appears:
Figure 11-2 Boot Loader Message of Run Application