11 Failures and LED Indications
11.2 Commissioning during Failures
220 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Wait for at least 20 s and then click the home link.
The user interface opens.
Starting User Interface with Loading a New/Different Firmware
Click Browse.... The Choose file dialog opens.
In the Choose file dialog, select the current firmware update (file extension .pck) in the Look in: list box
and click Open.
The path appears in the Browse... field.
Click upload.
The firmware is uploaded from the device to the PC and the following information is displayed in the Boot
Loader window:
Figure 11-3 Information in the Boot Loader
Wait for at least 30 s and then click the home
link.
The user interface opens.
11.2.2 Manual Start of the Boot Loader
If it is necessary to start the Boot Loader manually, proceed as follows:
If the SENTRON PAC5100/5200 is still energized by the supply voltage, switch off the supply voltage.
Press the F4 softkey on the SENTRON PAC5100/5200 (device with display) or the IP-Addr. push-button
(device without display) (see Chapter 5.7.3) and switch on the supply voltage while holding the F4 softkey
or IP address button down.
Hold the softkey F4 or the IP-Addr. push-button down until the LEDs ERROR (red) and H2 (yellow) on the
device top side are lit (LEDs RUN (green) and H1 (yellow) are off).
Release the softkey F4 or the IP-Addr. push-button.
SENTRON PAC5100/5200 starts the Boot Loader with the Boot Loader HTML page (Figure 11-1).