14 Operating Parameters
14.5 Administrative
258 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.5 Administrative
The following administrative settings are available:
Time Synchronization
Ethernet Communication
2) After enabling the parameter changes, any currently active Modbus TCP connections will be closed.
The Modbus TCP client must later re-open these connections.
2) After enabling the parameter changes, any currently active Modbus TCP connections will be closed.
The Modbus TCP client must later re-open these connections.Device and Language
14.5.1 Time Synchronization
Parameter Default Settings Setting Range
Source time synchronization Internal Internal
Ethernet NTP
Fieldbus
Time zone offset to UTC +00:00 -12 to +13 (hours)
(in increments of 0.5 h)
Daylight Saving Time switchover yes no
yes
DST offset to UTC +01:00 0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST March
Last week
Sunday
02:00 AM
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
End of DST October
Last week
Sunday
03:00 AM
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
Additional Parameters if the Source is Ethernet NTP
Primary NTP server IP Address 192.168.0.254 Any
Secondary NTP server IP Address 192.168.0.253 Any
No polling of the NTP server if 0.0.0.0
was entered
Error indication after 10 min 2 min to 120 min
Additional Parameter if the Source is Fieldbus
Error indication after 10 min 2 min to 120 min