4 Measurands and Recording
4.2 Measurands
39SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
4.2 Measurands
4.2.1 Measurands in 1-phase Systems
The SENTRON PAC5100/5200 can measure and calculate quantities in 1-phase systems, Chapter 4.2.3
contains a detailed list of all measurands.
Measured and Calculated Quantities
The operational measurands alternating voltage V
P
,
alternating current I
P
, and frequency are measured. All
other operational measurands, harmonics, THDS (Subgroup Total Harmonic Distortion), and power and energy
types are calculated from the measured operational measurands.
Operational Measured Values
Alternating voltage V
ph
(mains voltage referred to the neutral conductor/protective ground N; RMS value):
Va
Alternating current I
P
(current through the conductor, RMS value): Ia
Active power factor cos : cos (a)
Power factor PF: PFa
Phase angle : a
Frequency (system frequency): f
Flicker (only SENTRON PAC5200): Pst, Plt
Harmonics
Fundamental V
Harmonics V, magnitude: H_Va-x
Fundamental I
Harmonics I, magnitude: H_Ia-x
Subgroup Total Harmonic Distortion V: THDS_Va
Subgroup Total Harmonic Distortion I: THDS_Ia
Power Quantities
Active power P: Pa
Reactive power Q: Qa
Reactive power (fundamental) Q1: Q1a
Apparent power S: Sa
Energy Quantities
Active energy WP: WPa (supply and demand)
Reactive energy WQ: WQa (inductive and capacitive)
Apparent energy WS: WSa