7 Operation at Use of a PC
7.3 Configuration of the Device
149SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.6 Setting Administrative Parameters
In the Configure tab you can view and if necessary edit the administrative settings. You can select the
parameters in the Administrative menu in the navigation window. These parameters can be changed in the
input/output windows Time synchronization, Communication Ethernet and Device and language.
7.3.6.1 Time Synchronization
Default Settings and Setting Ranges of the Time Synchronization
NOTE
Observe the procedure for the device configuration described in Device Configuration Procedure when setting
the administrative parameters.
Table 7-17 Time Synchronization Settings
Parameter Default Setting Setting Range
Source time synchronization Internal Internal
Ethernet NTP
Fieldbus
Time zone offset to UTC +00:00 -12 to +13 (hours)
(in increments of 0.5 h)
Daylight Saving Time switchover yes no
yes
DST offset to UTC +01:00 0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST March
Last week
Sunday
02:00 AM
Acc. to list boxes
(see Operating Parameters)
End of DST October
Last week
Sunday
03:00 AM
Acc. to list boxes
(see Operating Parameters)
Additional Parameters if the Source is Ethernet NTP
Primary NTP server IP address 192.168.0.254 Any
Secondary NTP server IP address 192.168.0.253 Any
No polling of the NTP server if
0.0.0.0 was entered
Error indication after 10 min 2 min to 120 min
Additional Parameter if the Source is Fieldbus
Error indication after 10 min 2 min to 120 min