7 Operation at Use of a PC
7.3 Configuration of the Device
148 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
Depending on the parameterized Start record option, the Start time field shows the start time of the
recording. After activation, the recording starts automatically at the specified time. If the Start immediately
option is selected, the recording also only starts after activation.
After recording has started, the Recording status fields shows the entry Running.
If you want to stop the recording, click on Stop recording and execute the activation.
The Recording status field shows the entry Not running and Start recording is displayed on the user
interface.
Recording Power Quality Data
When the device is started for the first time, it is necessary for the recording of power quality data that the Time
synchronization of the device is set to the current time first
. If the time is incorrect, the power quality measure-
ments do not conform to the current time. Proceed as follows:
Refresh the time via Ethernet NTP or Field bus in line with Time Synchronization or with the device-
internal clock in line with Date/Time.
Configure all necessary parameters (for example, AC measurement, Communication, etc.) on the relevant
tabs, except for
the Recording parameters settings.
When setting the parameters, make sure that the settings are consistent with each other (for example,
setting of the flicker lamp model consistent with the primary nominal voltage).
At last
, parameterize the Recording parameters and activate the settings.
NOTE
The restart of the record is carried out after a power failure automatically.
The status will change from Not running to Running when user change and activate parameters.