7 Operation at Use of a PC
7.3 Configuration of the Device
134 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5 Recording and Reporting
7.3.5.1 Event Recorders
Default Settings and Setting Ranges
Table 7-10 Event Recorders
Parameter Default Setting Setting Range
Supply voltage
Swell threshold 110 % 105 % to 140 % in 5-% steps
Dip threshold 90 % 75 % to 95 % in 5-% steps
Interruption threshold 5 % 1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis 2 % 1 % to 6 % in 1-% steps
Frequency
Underfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Overfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
Voltage unbalance threshold 5 % 1 % to 5 % in 1-% steps