14 Operating Parameters
14.4 Recording and Reporting
252 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.4 Recording and Reporting
14.4.1 Event Recorders
14.4.2 Trigger Management
Parameter Default Setting Setting Range
Supply Voltage
Swell threshold 110 % 105 % to 140 % in 5-% steps
Dip threshold 90 % 75 % to 95 % in 5-% steps
Interruption threshold 5 % 1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis 2 % 1 % to 6 % in 1-% steps
Frequency
Underfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Overfrequency threshold 1 % 0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
Voltage unbalance threshold 5 % 1 % to 5 % in 1-% steps
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of the of the primary nominal
voltage
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 %
of the of the primary nominal
voltage
100.0 % to 10 000.0 % of the primary
nominal voltage
0.0 V to 1 000 000.0 V