14 Operating Parameters
14.5 Administrative
259SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.5.2 Ethernet Communication
1)
After the parameter changes have been enabled, the device resets.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Parameter Default Settings Setting Range
IP Address
1)
192.168.0.55 Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0 Any
Default gateway
1)
192.168.0.1 Any
Enable SNMP no no
yes
Bus protocol Modbus TCP Modbus TCP
-none-
Bus Protocol Modbus TCP
Use a user-port number
2)
no no
yes
User-port number
2)
(can only be set when Use a user-port
number is parameterized with yes)
10000 10000 to 65535
Access rights for user port
(can only be set when Use a user-port
number is parameterized with yes)
Full Full
Read only
Access rights for user port 502 Full Full
Read only
Keep Alive time 10 s 0 s = switch off
1 s to 65 535 s
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms