7 Operation at Use of a PC
7.3 Configuration of the Device
150 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
To change the time synchronization, proceed as follows:
In the navigation window, select the Administrative menu and click Time synchronization.
Figure 7-43 Configure Tab, Time Synchronization Input/Output Window, Ethernet NTP Selected
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table 7-17.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.