7 Operation at Use of a PC
7.3 Configuration of the Device
136 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.2 Trigger Management
Default Settings and Setting Ranges
Table 7-11 Trigger Management
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of the primary nominal
voltage
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 %
of the primary nominal
voltage
100.0 % to 10 000.0 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Hysteresis 2.00 %
of the primary nominal
voltage
0.0 % to 50.0 % of the of the primary
nominal voltage
Current trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold 110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
Hysteresis 2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Waveform capture setting
Total recording duration 2.0 s 0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Record ph-ph voltage no no
yes