7 Operation at Use of a PC
7.3 Configuration of the Device
138 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.3 Recorder Parameters
Default Settings and Setting Ranges
1)
The trend recorder also creates a PQDIF file when 1024 data points (voltage values with a time stamp)
have been generated within the recording interval.
Table 7-12 Recorder Management
Parameter Default Setting Setting Range
Measurement Recorder
Average intervals - Frequency 10 s fixed
Short term flicker 10 min fixed
Long term flicker 2 h fixed
Average interval - Voltage /
Unbalance / Harmonics
10 min 30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics Odd Even
Odd
All
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
The created PQDIF files can be
downloaded via the User Inter-
face.
24 h File generation
every:
At average interval
1 h (fix) 30 s
2 h (fix) 1 min
2 h 10 min, 15 min,
30 min, 1 h or
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF (see chapter 7.4.2.4)
CSV
All
Flicker lamp model 230 V 230 V
120 V
Trend Recorder
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
1% to 5% in 1 % steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
12 h, 24 h