7 Operation at Use of a PC
7.3 Configuration of the Device
145SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.5 Report Configuration
The Report configuration allows you to parameterize the PQ threshold parameters (User defined). You can
adjust the process connections to the installation environment and enter different operational settings.
Alternatively, you can use the default values according to EN 50160 LV&MV or EN 50160 HV.
Default Settings and Setting Ranges
1)
When an event has occurred, with this setting the recordings of the measurement recorder and trend re-
corder are marked in red on the Find result list (see Functioning of the Measuring System according to IEC
61000-4-30, 7.4.2.1 and 7.4.2.2).
2)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
Table 7-15 Report Configuration
Parameter Default Setting Setting Range
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
- Any text displayed in the
printout of the power quality
report
Power Quality Report
Evaluation mode according to: EN 50160 LV&MV EN 50160 LV&MV
EN 50160 HV
User defined
Flagging acc. to
IEC 61000-4-30
no no
yes
1)
Power frequency
99.5 % of measurand should be in -1.0 % to 1.0 % deviation of the power
frequency.
100 % of measurand should be in -6.0 % to 4.0 % deviation of the power
frequency.
Any setting for user-defined
evaluation mode
Power supply voltage magnitude
95 % of measurand should be in -10.0 % to 10.0 % deviation of the
declared input voltage Udin.
100 % of measurand should be in -15.0 % to 10.0 % deviation of the
declared input voltage Udin.
Any setting for user-defined
evaluation mode
Flicker severity
95 % of measurand should be less than 1.0
Voltage unbalance
2)
95 % of measurand should be less than 2.0 %.
100 % of measurand should be less than 3.0 %.
Any setting for user-defined
evaluation mode
Subgroup Total Harmonic Distortion factor (THDS)
95 % of measurand should be less than 8.0 %.
Any setting in % for user-
defined evaluation mode
Voltage event interruptions
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Any setting for user-defined
evaluation mode
Harmonic voltages
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Any setting for user-defined
evaluation mode