4 Measurands and Recording
4.1 Measuring and Recording System
35SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
4.1.2.4 Event Recorder
The Event Recorder exclusively records PQ events (undervoltage, overvoltage, voltage interruptions). The use
nominal voltage is the reference value for the analysis.
Figure 4-6 Recording of the Event Recorder, Overvoltage and Undervoltage
Voltage Event
Dip threshold: 75 % to 95 % (default 90 %)
Swell threshold: 105 % to 140 % (default 110 %)
Voltage interruption threshold: 1 % to 10 % (default 5 %)
Event hysteresis: 1 % to 6 % (default 2 %)
Frequency Event
Underfrequency threshold: 0.1 % to 5 % (default 1 %)
Overfrequency threshold: 0.1 % to 5 % (default 1 %)
Voltage Unbalance Event
Voltage unbalance threshold: 1 % to 5 % (default 5 %)