CM 1xDALI command list
3.3 Diagnostic
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
25
3.2.5 Go to control gear scene
Description
Use this CM command to go to the configure scene for control gears.
Command ID
5
Input Param-
eters
Byte 0
0 (16#00) to 63 (16#3F): short address of the control gear
128 (16#80) to 143 (16#8F): group address
253 (16#FD): unaddressed devices
255 (16#FF): all devices
Byte 1
Scene number
Response
Parameters
Byte 0 Error code (Page 51)
3.3 Diagnostic
You use diagnostic commands to query the status information of the DALI devices.
3.3.1 Query control gear status
Description
Use this CM command to query the control gear status by sending DALI commands
to the device. The response is the latest status and it updates the status stored in the
CM 1xDALI.
Command ID
11
Input Param-
eters
Byte 0 Short address of the control gear
Response
Parameters
Byte 0
Return code (Page 51)
Byte 1
Bit 0: configured flag: this Bit is 1 when the short address is configured
by "Add control gear (Page 32)" or "Start upload control gear parame-
ters (Page 41)".
Bit 1: short address changed flag
0: if CM 1xDALI changed the short address of the device.
1: if CM 1xDALI assigned the device a new short address after
scanning.
Bit 2 to 7: Reserved
Byte 2 Address status
1: normal status
2: no device with the short address
3: The DALI device replies an error frame. This error can be caused by
a short address conflict or a problem of DALI device.
4: type mismatch: the configured type is not the same as the actual
one.