3.4.4 Set control gear basic parameters
Description
Use this CM command to set the general parameters of a control gear. The command
sets the parameters in the device and saves the parameters in CM 1xDALI.
Command ID
24
Input Param-
eters
Byte 0 Short address
Byte 1
Power on level
Byte 2
System failure level: level when the device is in system failure status.
Byte 3
Minimum level
Byte 4
Maximum level
Byte 5 Fade rate
Byte 6 Fade time
Byte 7
Extended fade time base
Byte 8 Extended fade time multiplier
Response
Parameters
Byte 0 Return code (Page 51)
3.4.5 Query control gear extended parameters
Description
Use this CM command to query the type-related parameters of a control gear.
Only control gear types 1 to 8 have type-related parameters. Control gears of other
type return a 16#87 (not supported) error in the response parameters.
Command ID
25
Input Param-
eters
Byte 0
Short address of the control gear
Byte 1 Query actual device flag:
0: query the parameters saved in the CM 1xDALI.
1: query the parameters on the device by DALI commands.
Response
Parameters
Byte 0
Return code (Page 51)
Byte 1
0: query the parameters saved in CM 1xDALI.
1: query the parameters on the device.
Byte 2
Control gear type
Byte 3 to 34 Type-related parameters (Page 35)