CM 1xDALI command list
3.7 Return code and control status
ET 200SP CM 1xDALI Communication Model Description
52 Programming Manual, 12/2019, A5E47581955-AA
3.7.2 Address status
Error code
Description
16#00
Status is unknown. Query or scan the DALI bus.
16#01 If this short address is configured, the device with this short address is the same
as configured. If this short address is not configured, a device with this address is
present on the DALI bus.
16#02
No device with this short address is on the DALI bus.
16#03
More than one device with this short address is on the DALI bus.
16#04
The configured type is not the type of the actual device on the DALI bus.
16#05 The configured number of instances does not correspond to the actual device.
Only input devices have this status.
16#0F
This short address is assigned to DALI module itself.
3.7.3 Description of status
Control gear status
Bit
Description
0
Control gear failure
1
Lamp failure
2
Lamp on
3
Limit error
4
Fade running
5
Reset state
6
No short address
7
Power cycle seen
Control gear type related status
Bit
Type 1 (emergency)
Type 2 (discharge)
Type 3 (halogen)
type 4 (incandescent)
0 Circuit failure Mains voltage too low Short circuit Load over-current
shutdown
1 Battery duration fail-
ure
Mains voltage too
high
Open circuit Open circuit
2 Batter failure Converter thermal
overload
Load decrease Load decrease
3 Emergency lamp
failure
Reserved Load increase Load increase
4 Function test maxi-
mum delay exceeded
Ignition time out Current protector
active
Reserved