CM 1xDALI command list
3.4 Configuration
ET 200SP CM 1xDALI Communication Model Description
42 Programming Manual, 12/2019, A5E47581955-AA
3.4.15 Add input device
Description
Use this CM command to configure or modify an input device and its instances.
Adding an input device sets the configured flag of the device but does not send a
DALI command to the device on the bus.
After the configuration, you can set parameters for this short address.
If the short address exists, this command overwrites the configured instance.
Command ID
35
Input Param-
eters
Byte 0 Short address of the input device
Byte 1
Number of instances
Byte 2 to 33 Types of the instances. Each byte indicates one instance. For exam-
ple, Byte 2 is for instance 0; Byte 3 for instance 1.
Response
Parameters
Byte 0
Return code (Page 51)
Byte 1 Control status after the configuration
3.4.16 Remove input device
Description
Use this CM command to cancel the configuration of an input device and its in-
stances. It also resets the saved configuration of this short address.
Command ID
36
Input Parameters
Byte 0
Short address of the input device
Response Pa-
rameters
Byte 0
Return code (Page 51)
Byte 1 Control status after the configuration.
3.4.17 Query input device parameters
Description
Use this CM command to query the general parameters of a input device.
Command ID
37
Input Param-
eters
Byte 0
Short address of the input device
Byte 1 Query actual device flag.
0: query the parameters saved in CM 1xDALI.
1: query the parameters of the device.
Response
Parameters
Byte 0
Return code (Page 51)
Byte 1
0: query the parameters saved in the CM 1xDALI.
1: query the parameters of the device.
Byte 2
Operating mode
Byte 3 Power on cycle notification flag:
If this flag is no set to 1, the input device can send a power cycle noti-
fication event when it powers on.
Byte 4
Number of instances