CM 1xDALI command list
3.4 Configuration
ET 200SP CM 1xDALI Communication Model Description
40 Programming Manual, 12/2019, A5E47581955-AA
Byte 4 to 5 Show the value of the color type.
Color coordinate-x (when the scene color type is color-coordinate
(16#10).)
Color temperature (when the scene color type is color-temperature
(16#20).)
0 (when the scene color type is unknown.)
Byte 6 to 7 Show the value of color type.
Color coordinate-y (when scene color type is color-coordinate
(16#10).)
16#00 (when the scene color type is unknown.)
3.4.11 Set control gear scene
Description
Use this CM command to set the scene level and color of a color-control control gear.
If you can call this command with a scene level of 255 (16#FF), this command re-
moves the scene from the addressed control gear.
Note: This command has no effect on those control gears which are not color-control
(type 8) control gears.
Command ID
31
Input Param-
eters
Byte 0
Short address
Byte 1
Scene number
Byte 2
Scene level
Byte 3 Sets the scene color type
16#10: color coordinate-xy.
16#20: color-temperature.
Byte 4 to 5 Sets the value of color type
Color coordinate-x (when Byte 1 is 16#10)
Color temperature (when Byte 1 is 16#20)
Byte 6 to 7 Sets the value of color type
Color coordinate-y (when Byte 1 is 16#10)
Scene color type is not color coordinate-xy. (when Byte 1 is
16#00)
Response
Parameters
Byte 0 Return code (Page 51)