CM 1xDALI command list
3.4 Configuration
ET 200SP CM 1xDALI Communication Model Description
34 Programming Manual, 12/2019, A5E47581955-AA
3.4.3 Query control gear basic parameters
Description
Use this CM command to query the general parameters of a control gear.
Command ID
23
Input Param-
eters
Byte 0
Short address of the control gear
Byte 1 Query actual device flag:
0: query the parameters saved in the CM 1xDALI.
1: query the parameters on the device by DALI commands.
Response
Parameters
Byte 0 Return code (Page 51)
Byte 1
0: query the parameters saved in the CM 1xDALI.
1: query the parameters on the device.
Byte 2
Power on level: the level when the device is powered on.
Byte 3
System failure level
Byte 4
Minimum level
Byte 5
Maximum level
Byte 6 Fade rate
Byte 7 Fade time
Byte 8
Extended fade time base
Byte 9
Extended fade time multiplier
Byte 10
Control gear type
Byte 11
Device version of the control gear (when byte 1 is 1)
0 (when the byte 1 is 0)
Byte 12 Physical minimum level: If queried parameters are saved in CM
1xDALI, the device version is 0.