CM 1xDALI command list
3.5 Addressing
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
47
Input Param-
eters
Byte 0 Specify the device type.
1: control gears
2: input devices
Byte 1 Specify the short address to scan
0 (16#00) to 63 (16#3F): short address
253 (16#FD): only unaddressed
255 (16#FF): all short addresses and unaddressed.
Response
Parameters
Byte 0 Return code (Page 51)
3.5.2 Start identify device
Description
Use this CM command to start an identify process for a DALI device.
The exact identify process is manufacturer-specific.
You can check the process by "querying the current command status (Page 49)"or
cancel the process by "canceling the current command (Page 51)".
Command ID
52
Input Param-
eters
Byte 0 Specify the device type.
1: control gears;
2: input devices.
Byte 1
0 (16#00) to 63 (16#3F): short address;
128 (16#80) to 143 (16#8F): group number;
253 (16#FD): unaddressed devices;
255 (16#FF): all devices.
Response
Parameters
Byte 0 Return code (Page 51)