CM 1xDALI command list
3.4 Configuration
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
33
3.4.2 Remove control gear
Description
Use this CM command to delete a configured control gear which is added by "Add
control gear (Page 32)" and its data saved in the CM 1xDALI. Refer to chapter
5.1
CM 1xDALI data storage model
in the manual of ET 200SP Communication mod-
ule CM 1xDALI (https://support.industry.siemens.com/cs/ww/en/view/109769428)
to understand the storage model of CM 1xDALI.
This CM command resets the saved configuration on the input short address.
This CM command does not send any command to the DALI bus.
Command ID
22
Input Parameters
Byte 0
Short address of the control gear
Response Pa-
rameters
Byte 0
Return code (Page 51)
Byte 1 Address status after the configuration