EasyManuals Logo

Siemens SIMATIC S5-95F User Manual

Siemens SIMATIC S5-95F
579 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #371 background imageLoading...
Page #371 background image
S5-95F S5-95F on SINEC L1
Coordination of Frame Sequence (115F-14 and 115F-15 Modes)
The S5-95F resets bit 0 or 2 of the UVB after sending the frame, even if the receiver's operating
system has not accepted the data of the old frame.
Safety Note
When you use message modes 115F-14 and 115F-15, the S5-95F useful frame
monitoring feature is deactivated. To prevent an undetected frame loss, you must not
alter the send mailbox more than once during each safety time for Receive.
EWA 4NEB 812 6210-02
13-17