EasyManua.ls Logo

Siemens SIMATIC S5-95F - Addressing and Address Assignments

Siemens SIMATIC S5-95F
579 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S5-95F Rules for Failsafe Operation of an S5-95F
18.14 Addressing and Address Assignments
The S5-95F's I/Os are subdivided into onboard I/Os and external I/Os.
In order that it be possible to address specific inputs and outputs, the I/Os must be assigned
addresses. Please refer to Chapter 6 for details on addressing and address assignments.
The addresses of the onboard I/Os are fixed, and cannot be changed. The addresses of the external
I/Os are slot-dependent.
Address Assignment for External I/O Modules
When you mount an external I/O module in a slot on a bus unit, the module is immediately assigned
a slot number and consequently a fixed byte address in the process image I/O tables.
Connect the sensors and actuators either via a connector or to the terminal block of the bus units.
The terminal selected determines the bit address (channel number) of the input or output.
Figure 18-4. Address Assignment
I/O module
=
Process image I/O
tables in the PLC
Slot number
+
channel number
Control
program
Address in a
statement
Address in the
process image output
table
Address in the
process image input
table
Data flow from module - PLC
Addressing of Single-Channel External I/Os
Single-channel I/Os are never failsafe. In the user program, these I/Os must always be referenced
under the address under which they are used in the relevant subunit.
Addressing of Two-Channel, Failsafe External I/Os
Two-channel I/Os can be used only with failsafe onboard I/Os or with redundant failsafe external I/O
modules.
Note
You must always address failsafe external I/Os in the user program at the address where
they are used in subunit A (failsafe external I/Os have always an even-numbered byte
address)!
EWA 4NEB 812 6210-02
18-29

Table of Contents

Related product manuals