Differences Between the S5-95U and the S5-95F S5-95F
16.5 Programmer Functions and Error Diagnostics
16.5.1 Programmer Functions
On the S5-95F, the programmer functions are restricted in failsafe mode. An overview of
permissible programmer functions can be found in Table 14-7.
16.5.2 Error Diagnostics
Additional system event DB (DB254)
Errors are flagged in the system event DB (see section 15.3).
You can read and display the system event DB with the COM 95F software.
OB37 is invoked prior to an S5-95F error response.
16.6 Battery Failure
A battery must be installed for failsafe mode (see section 2.5.4).
If no battery has been inserted, or if the battery is too weak, the S5-95F calls OB34. Seventy-two
hours after failure of the battery or failure to install a battery, the S5-95F goes to STOP.
16-4
EWA 4NEB 812 6210-02