S5-95F Module Spectrum
A Module Spectrum
A.1 General Technical Specifications for Failsafe Modules
Climatic Environmental Conditions
Electromagnetic Compatibility (EMC)
Noise Immunity
Temperature
Operating
- horizontal design 0 to+60 °C (32 to 104 °F)
- vertical design 0 to+40 °C (32 to 104 °F)
(Air-intake temperature,
measured on the underside
of the module)
Storage/transport - 40 to+70 °C
(-40 to 150 °F)
Temperature change
- operating max. 10 °C/h (50 °F/h)
- storage/transport max. 20 °C/h (68 °F/h)
Relative humidity to DIN 40040
15 to 95 % (indoor),
non-condensing
Atmospheric pressure
- operating 860 to 1060 hPa
- storage/transport 660 to 1060 hPa
Pollutants
-SO
2
0.5 ppm,
(rel. humidity 60 %,
non-condensing)
-H
2
S 0.1 ppm,
(rel. humidity 60,
non-condensing)
Mechanical Environmental Conditions
Vibration to IEC 68-2-6
- tested with 10 to 150 Hz,
(const. ampl. 0.15 mm)
57 to 150 Hz,
(const. accel. 2 g)
Shock to VDE 0116
- tested with 18 shocks
(semisinusoidal 30 g/18 ms)
Free-fall to IEC 68-2-31
- tested with height of fall 50 mm
Rated electromagnetic to IEC 801-3,
field test severity rating 3
field strength 10 V/m
Fast transient burst to IEC 801-4,
severity rating 3
Power supply lines
- Supply voltage 24 V DC 2 kV
Signal lines
- Analog input/output modules 1 kV
- Digital input/output modules
for V 24 V 2 kV
Comunications
interfaces 1 kV
Surge impulse to IEC 801-5,
severity rating 3
HF current to IEC 801-6,
severity rating 3
Electromagnetic Compatibility (EMC)
Noise Immunity
Electrostatic discharge to IEC 801-2
severity rating 3
- Test voltage 8 kV air discharge
6 kV contact discharge
IEC/VDE Safety Information
Degree of protection to IEC 529
- Type IP 20
- Class I to IEC 536
Insulation rating to VDE 0160
- between electrically (05. 1988)
independent circuits
and
with circuits connected
to a central grounding
point to VDE 0160
- between all circuits (05. 1988)
and
a central grounding point
(standard mounting rail) to VDE 0160
(05. 1988)
Test voltage Sine, 50 Hz
for a rated voltage
V
input
of the circuits (AC/DC)
V
input
=0 to 50 V 500 V
V
input
=50 to 125 V 1250 V
V
input
=125 to 250 V 1500 V
Emitted Electromagnetic Interference
Radio interference level
to EN 55011 Limit class A
EWA 4NEB 812 6210-02