Technical Specifications
Number of outputs 4
Galvanic isolation yes (transformer)
- in groups of 4
Load voltage L+
- rated value 24 V DC
- permissible range 20 to 30 V
Output current
for "1" signal
- rated value 2 A at 40 °C/104 °F
1.5 A at 60 °C/140 °F
- permissible range 5 mA to 2 A
- lamp load max. 20 W
Residual current at
"0" signal max. 1 mA
Short-circuit protection
- thermal
- electronic
Voltage induced on circuit
interruption (internal)
limited to - 36 V
Switching frequency
- resistive load max. 100 Hz
- inductive load (2 mH) max. 2 Hz
Total permissible
current of outputs at 40 °C/104 °F: 8 A
at 60 °C/140 °F: 6 A
Driving of digital input possible
Parallelling of outputs possible, if outputs
decoupled by diodes
Permissible ambient
temperature of PLC
- horizontal arrangement 0 to 60 °C
(32 to 140 °F)
- vertical arrangement 0 to 40 °C
(32 to 104 °F)
Length of cable
- unshielded max. 200 m (660 ft.)
Insulation rating to VDE 0160
Rated insulation voltage
(+9 V to L+) 60 V AC
- Insulation group 2×B
- tested with 500 V AC
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1×B
- tested with 500 V AC
Current consumption
- from+9 V (CPU) max. 60 mA
- from L+(without load) max. 36 mA
Power loss
of the module typ. 5 W
Weight approx. 325 g (11.4 oz.)