Output side
Number of outputs 16
Galvanic isolation no
- in groups of 8
Load voltage L+
- rated value 24 V DC
- permissible range 20 to 30 V
(ripple included)
- value at t<0.5 s 35 V
Output current I
N
for ”1” signal
- rated value 500 mA
- permissible range 5 to 500 mA
Residual current
for ”0” signal max. 0.5 mA
Short-circuit protection yes
Short-circuit indication red LED
Output voltage for
”1” signal L+(- 0.6 V)
Voltage induced on circuit
interruption (internal)
limited to - 15 V
Switching frequency with
- resistive load 100 Hz
- inductive load 2 Hz
Permissible total current
of the outputs 6 A
Driving of a digital input possible
Paralleling of outputs possible in pairs
- maximum current (0.8×I
N
)
Current consumption
- from +9 V (CPU) typ. 10 mA
- from L+ (without load) typ. 100 mA
Lamp load max. 5 W
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 1
tested with 8 kV air discharge
2 kV contact discharge
Electromagnetic fields
to IEC 801-3 Severity rating 3
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 2
tested with 1.2 kV on supply lines
1 kV on signal lines
Input side
Number of inputs 16
Galvanic isolation no
- in groups of 16
Input voltage L+
- rated value 24 V DC
- for ”0” signal 0 to 5 V
- for ”1” signal 13 to 30 V
Input current
for ”1” signal typ. 4.5 mA
Inherent delay
- from ”0” to ”1” typ. 4 ms
- from ”1” to ”0” typ. 3 ms
Fault LED (red) indicates
interruption of
L+/M supply
Connection of
two-wire BERO
proximity switches possible
- residual current 1.5 mA
Current consumption
- from +9 V (CPU) typ. 50 mA
Technical Specifications
Cable length
- unshielded 100 m (330 ft.)
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1 × B
Power loss of the
module typ. 4.5 W
Weight approx. 190 g (7 oz.)