EasyManua.ls Logo

Siemens SIMATIC S5-95F - Page 523

Siemens SIMATIC S5-95F
579 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Module Spectrum S5-95F
Analog Output Module 2 x±20 mA (continued) (6ES5 470-8MB12)
Technical Specifications
Output range
(rated values) ±20 mA
Number of outputs 2
Galvanic isolation yes (outputs to
grounding point and
between outputs)
Load resistance 300
Connection method two-wire
connection
Digital representation 11 bits + sign
of output signal (1024 units =
rated value)
Measured value two's complement
representation (left-justified)
Conversion time
(0 to 100 %) max. 0.15 ms
Permissible overload 25 %
No-load voltage ±15 V
Permissible voltage
difference to ground
and between outputs max. 75 V DC/60 V AC
Basic error limits ±0.3 %
(operational error limits
at 25 °C (77 °F), referred
to output range)
Operational error limits
(0 to 60 °C (32 to 140 °F),
referred to output range) ±0.6 %
Length of cable
- shielded max. 200 m (660 ft.)
Supply voltage L+
- rated value 24 V DC
- ripple V
PP
3.6 V
- permissible range 20 to 30 V
(ripple included)
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1 x B
- tested with 500 V AC
Rated insulation voltage
(Output to L +, between
outputs, output to + 9 V) 60 V AC
- insulation group 1 x B
- tested with 500 V AC
Current consumption
- from + 9 V (CPU) typ. 170 mA
- from L + typ. 130 mA
Power loss
of the module typ. 3.8 W
Weight approx. 290 g (10 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 2
tested with 8 kV air discharge
4 kV contact
discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 3
tested with 2 kV on supply lines
1 kV on signal lines
A-28
EWA 4NEB 812 6210-02

Table of Contents

Related product manuals