Module Spectrum S5-95F
Analog Output Module 2 x 4 ... 20 mA (continued) (6ES5 470-8MC12)
Technical Specifications
Output range
(rated value) 4 to 20 mA
Number of outputs 2
Galvanic isolation yes (outputs to
grounding point and
between outputs)
Load resistance 300
Capacitive load incl.
cable capacitance < 100 nF
Connection method two-wire connection
Digital representation
of output signal 11 bits + sign
(1024 units = rated
value)
Measured value two's complement
representation (left-justified)
Conversion time
(0 to 100 %) max. 0.15 ms
Permissible overload 25 %
No-load voltage ± 15 V
Permissible voltage
difference to central
ground point and
between outputs max. 75 V DC/60 V AC
Basic error limits ±0.2 %
(operational error limits
at 25 °C (77 °F), referred
to output range)
Operating error limits
(0 to 60 °C (32 to 140 °F),
referred to output range) ±0.6 %
Length of cable
- shielded max. 200 m (660 ft.)
Supply voltage L+
- rated value 24 V DC
- ripple V
PP
3.6 V
- permissible range 20 to 30 V
(ripple included)
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1 x B
- tested with 500 V AC
Rated insulation voltage
(outputs to L+,
between outputs,
output to + 9 V) 60 V AC
- insulation group 1 x B
- tested with 500 V AC
Current consumption
- from + 9 V (CPU) typ. 170 mA
- from L+ typ. 130 mA
Power loss of
the module typ. 3.8 W
Weight approx. 290 g (10 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 2
tested with 8 kV air discharge
4 kV contact discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 3
tested with 2 kV on supply lines
1 kV on signal lines
A-30
EWA 4NEB 812 6210-02