Technical Specifications
Current supply to the
expansion unit max. 2.5 A
Number of interface
modules per PLC max. 4
Cable connectors for the
IM 316
- Cable connector
(0.5 m/1.6 ft.) 6ES5 712-8AF00
- Cable connector
(2.5 m/8.2 ft.) 6ES5 712-8BC50
- Cable connector
(5.0 m/16.4 ft.) 6ES5 712-8BF00
- Cable connector
(10 m/33 ft.) 6ES5 712-8CB00
Cable insulation in ducts permissible
Permissible potential
difference between
(IM 316) and central
ground point (CPU) ±1 V
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1×B
Dimensions
W×H×D (in mm) 45.4×135×39
(in in.) 1.8 × 5.3 × 1.5
Current consumption
- from +9 V (CPU) typ. 27 mA
Weight approx. 120 g (4.2 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 3
tested with 8 kV air discharge
6 kV contact
discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
For EMC purposes unused Sub D sockets on the
IM 316-8MA12 must be covered with a spare sub D
socket connector (6ES5-750-2AA21).