CPU display
Automation system
292 System Manual, 01/2023, A5E03461182-AK
Regarding : CPU status information
The following table shows the CPU status information that can be retrieved via the display.
Table 13- 1 CPU status information
Color and icons for the status data
Meaning
Green
RUN
Orange
STOP
STOP - firmware update
Red
FAULT
White
Connection established between CPU and display.
Protection level configured.
At least one interrupt is active in the CPU.
No SIMATIC Memory Card inserted in the CPU.
The serial number to which a know-how-protected block is bound does not
match the serial number of the CPU or the SIMATIC Memory Card.
No user program loaded.
Force job is active in the CPU.
F-capability activated. Safety operation active (for fail-safe CPUs)
The symbol is grayed out when safety mode is deactivated.
Fail-safe CPU (for fail-safe CPUs).